Rev. B, 4/13 MPX Series Magnetostrictive Level Sensors
9
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Sensor Communicaons
Modbus
(RS-485)
The MPX-E1 and MPX-R1 series ulizes standard Modbus RTU protocol (RS-
485). The sensor can only operate as a slave device. For more informaon
about Modbus RTU, please visit www.modbus.org.
The sensor will transmit at: 9600 baud, 8 bits, 1 Stop Bit, No parity (allow a
minimum delay of 300 ms between transacons).
12-24 Vdc
Out
Power Source
(14- 24 Vdc)
Sensor
RST-4100
Programming Module
Wiring
(MPX-E2, MPX-R2, MPX-E3, and MPX-R3)
To USB
Out 24V
RST-4100
Load Resistor
(100 Ω to 700 Ω)
+
Note: a minimum of
14 Vdc is required to
establish communications
4-20 mA (requires RST-4100 module)
MPX-E2, MPX-R2, MPX-E3, and MPX-R3 sensor versions require the RST-4100
module and the APG Modbus soware for programming.
A load resistance is required at the DC Common (GND) end of the current
loop in order to establish communicaons. The RST-4100 is wired in parallel
between the power source and the sensor, with the load resistance between
the “Out” leg connecon and the power source ground (as shown below).