MPX Series Magnetostrictive Level Sensors Rev. B, 4/13
8
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Hazardous Locaon Wiring
Installation in: Class I Division 1 & 2 Groups C and D, Max. Temp. 85
0
C
Ex d IIB : Ex nA IIB
Class I, Zone 1; AEx d IIB : Class I, Zone 2; AEx nA IIB
Hazardous Area
Hazardous Area
Non-Hazardous Area
Non-Hazardous Area
CSA/UL Listed Conduit
Earth Ground
Connection
Earth Ground
Connection
Earth Ground
Connection
CSA/UL Listed Hazardous Location Cable
Non-Incendive Wiring for Installation in
Class I Division 2 Groups C and D, Max. Tep. 85
0
C
Certied Associated
Non-Incendive
Field Wiring Apparatus
Vmax ≥ Voc,
Ca ≥ Ccable + Ci
La ≥ Lcable + Li
Vmax = 28VDC,
Imax = 200ma,
Ci = 0nF, Li = 0
A
A
B
Install in accordance with Section 18 of the CEC or Article 500 of the NEC.
CSA listed or NRTL/UL listed conduit seal at location A & B.
Do NOT disconnect while circuit is live unless area is known to be non-hazardous
Tapering or replacement with non-factory components may adversely aect the safe use of the system.