MPX Series Magnetostrictive Level Sensors Rev. B, 4/13
34
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
•Web Alarming (40430 to 40435)
When the MP is interfaced with an LOE or RST-5002 web-enabled master
device, the MP can be congured to generate website alarms via levelandow.
com. Refer to the LOE or RST-5002 user manual for more informaon about
website alarms and using levelandow.com.
Trip Alarm 1 (40430) or Alarm 2 (40433) Distance
Sets the level (in mm), beginning the boom of the stem, to the rst (lowest)
actuaon point (refer to next page for more informaon).
Trip Alarm 1 Window (40431 or 40434)
Sets the level (in mm), beginning from the Trip Distance locaon, to the sec-
ondary actuaon point (refer to next page for more informaon).
Trip Alarm 1 Type (40432 or 40435)
Determines the operaonal logic performed by the Trip Alarm (refer to next
page for more informaon).
Conguring Trip Alarm Types for Website Alarming:
(refer to Trip Types on next page)
Placing a “1” in front of any of the Trip Types designates an acve trip point as
an alarm condion. For example; Trip Type 3 would be designated as 13, and
would iniate a website alarm whenever the trip is acve (on).
Placing a “2” in front of any of the Trip Types designates an inacve trip point as
an alarm condion. For Example; Trip Type 3 would be designated as 23, and
would iniate a website alarm whenever the trip is inacve (o).